Electric Vehicle Infrastructure Training Program Certified Exam Prep
Free practice questions

Free EVITP Certified Practice Questions

10 exam-style questions with answers and explanations, straight from our 1,050-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.

Start the free practice test → ★★★★★4.9/5 from 2,400+ candidates · No signup

These 10 free EVITP Certified questions are organized by exam domain, so you can see how each part of the Electric Vehicle Infrastructure Training Program Certified blueprint is tested. Reveal the answer and explanation under each question.

Domain 1: Introduction to Electric Vehicles

Question 1

A homeowner replaces a 32 A EVSE with a 48 A unit on a properly sized new circuit. The installation passes inspection and the control pilot is verified correct, but charging is no faster than before. What is the MOST likely explanation?

Show answer & explanation

Correct answer: A - The vehicle's on-board charger limits the AC charging rate

Domain 2: EV Charging Equipment

Question 2

An EVSE transmits a control pilot signal with a 40% duty cycle. What maximum current is being advertised to the vehicle?

Show answer & explanation

Correct answer: B - 24 A

Question 3

What is the PRIMARY reason a 20 mA trip threshold is permitted for the personnel protection system in listed Level 2 EVSE, when a Class A GFCI trips at 4-6 mA?

Show answer & explanation

Correct answer: B - A ground-monitoring circuit continuously verifies EGC integrity

Question 4

A technician measures a steady +9 V on the control pilot conductor at an EVSE with a vehicle plugged in. This indicates:

Show answer & explanation

Correct answer: B - State B - vehicle connected, not ready to charge

Domain 3: 2023 NEC Review

Question 5

Per 23 CFR 680.106(j), all of the following satisfy the electrician qualification requirement for federally funded EV charger installation EXCEPT:

Show answer & explanation

Correct answer: C - A current state journeyman electrician license held for over ten years

Question 6

An EVSE rated 100 A at 208 V is installed on the exterior of a commercial building, 60 feet from the panelboard. Regarding a disconnecting means, the installation requires:

Show answer & explanation

Correct answer: B - A readily accessible disconnecting means capable of being locked in the open position

Domain 4: Load Calculations and Recognizing Existing Conditions

Question 7

A 48 A Level 2 EVSE is to be permanently wired. What is the minimum branch-circuit overcurrent protective device rating?

Show answer & explanation

Correct answer: B - 60 A

Question 8

An electrical contractor is cited by an inspector for a branch circuit to an EVSE with a calculated voltage drop of 4%. The contractor disputes the citation. Which statement is correct?

Show answer & explanation

Correct answer: D - The contractor is correct; the 3% figure appears in an Informational Note and is not enforceable

Question 9

A 6 AWG THHN copper conductor (90°C rated, 75 A) supplies a hardwired 48 A EVSE. Ambient temperature is normal and there are no more than three current-carrying conductors in the raceway. The equipment terminations are rated 60°C. What ampacity governs this conductor?

Show answer & explanation

Correct answer: A - 55 A, based on the 60°C column

Question 10

A contractor wants to add EVSE to an existing commercial service without a load calculation of the entire facility. Twelve months of utility demand data is unavailable. Per NEC 220.87, what is the minimum acceptable alternative?

Show answer & explanation

Correct answer: A - A 30-day recording at 15-minute intervals including the highest-demand season

The rest of the EVITP Certified blueprint

The EVITP Certified exam also covers these domains. Drill them in the full free practice test:

That's 10 of 1,050

The full bank has 1,040 more EVITP Certified questions with explanations.